Who it’s for: Licensed HVAC/R techs, apprentices and contractors who need a fair dinkum dual-port manometer for gas, static and differential pressure—with a built-in pump to test and calibrate pressure switches. It’s quick, accurate and built for Aussie conditions, so jobs get signed off with no dramas.
On a chilly Melbourne service call, the inducer would spin up but the heater kept locking out. With the SDMN6 we induced a controlled vacuum, watched the Closed LED snap on, and captured the switching pressures. The culprit? A drifted adjustable switch. Two turns on the adjuster to manufacturer spec and the unit was back heating before smoko. That’s the difference: quicker diagnostics, safer operation, and fewer after-hours revisits.
Level up your commissioning kit with our Manometers collection for more options that suit your workflow.
Zero with hoses attached before low-pressure measurements, keep the two hoses to the switch the same length, and use Auto-Capture (HOLD) to snag the exact open/close pressures while you tweak the pump speed.
| Pressure range | ±60 inWC (gas); differential P1-P2 displayed |
| Static pressure resolution | 0.010 inWC |
| Units | inWC, mmWC, mbar, psi |
| Accuracy | ±1.5% FS (0–50°C) |
| Max pressure | 900 inWC (≈17.4 psi) – do not exceed |
| Power / battery life | 9V alkaline; ~200h (manometer), ~12h (switch test) |
| Features | ZERO, HOLD, backlight, Auto-Power-Off, continuity leads, “Closed” LED |
| Media | Dry, non-corrosive gases |
| Warranty | 1 year |